@ -0,0 +1,75 @@
|
||||
import type { OIDSet, UpsModel } from './types.js';
|
||||
|
||||
/**
|
||||
* OID sets for different UPS models
|
||||
* Contains mappings between UPS models and their SNMP OIDs
|
||||
*/
|
||||
export class UpsOidSets {
|
||||
/**
|
||||
* OID sets for different UPS models
|
||||
*/
|
||||
private static readonly UPS_OID_SETS: Record<UpsModel, OIDSet> = {
|
||||
// Cyberpower OIDs for RMCARD205 (based on CyberPower_MIB_v2.11)
|
||||
cyberpower: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.3808.1.1.1.4.1.1.0', // upsBaseOutputStatus (2=online, 3=on battery)
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.3808.1.1.1.2.2.1.0', // upsAdvanceBatteryCapacity (percentage)
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.3808.1.1.1.2.2.4.0', // upsAdvanceBatteryRunTimeRemaining (TimeTicks)
|
||||
},
|
||||
|
||||
// APC OIDs
|
||||
apc: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.318.1.1.1.4.1.1.0', // Power status (1=online, 2=on battery)
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.318.1.1.1.2.2.1.0', // Battery capacity in percentage
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.318.1.1.1.2.2.3.0', // Remaining runtime in minutes
|
||||
},
|
||||
|
||||
// Eaton OIDs
|
||||
eaton: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.534.1.1.2.0', // Power status
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.534.1.2.4.0', // Battery capacity in percentage
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.534.1.2.1.0', // Remaining runtime in minutes
|
||||
},
|
||||
|
||||
// TrippLite OIDs
|
||||
tripplite: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.850.1.1.3.1.1.1.0', // Power status
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.850.1.1.3.2.4.1.0', // Battery capacity in percentage
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.850.1.1.3.2.2.1.0', // Remaining runtime in minutes
|
||||
},
|
||||
|
||||
// Liebert/Vertiv OIDs
|
||||
liebert: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.2.1', // Power status
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.4.1', // Battery capacity in percentage
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.5.1', // Remaining runtime in minutes
|
||||
},
|
||||
|
||||
// Custom OIDs (to be provided by the user)
|
||||
custom: {
|
||||
POWER_STATUS: '',
|
||||
BATTERY_CAPACITY: '',
|
||||
BATTERY_RUNTIME: '',
|
||||
}
|
||||
};
|
||||
|
||||
/**
|
||||
* Get OID set for a specific UPS model
|
||||
* @param model UPS model name
|
||||
* @returns OID set for the model
|
||||
*/
|
||||
public static getOidSet(model: UpsModel): OIDSet {
|
||||
return this.UPS_OID_SETS[model];
|
||||
}
|
||||
|
||||
/**
|
||||
* Get standard RFC 1628 OID set as fallback
|
||||
* @returns Standard OID set
|
||||
*/
|
||||
public static getStandardOids(): Record<string, string> {
|
||||
return {
|
||||
'power status': '1.3.6.1.2.1.33.1.4.1.0', // upsOutputSource
|
||||
'battery capacity': '1.3.6.1.2.1.33.1.2.4.0', // upsEstimatedChargeRemaining
|
||||
'battery runtime': '1.3.6.1.2.1.33.1.2.3.0' // upsEstimatedMinutesRemaining
|
||||
};
|
||||
}
|
||||
}
|
Reference in New Issue