fix(snmp): Fix Eaton UPS support by updating power status OID and adjusting battery runtime conversion.
This commit is contained in:
@@ -25,9 +25,9 @@ export class UpsOidSets {
|
||||
|
||||
// Eaton OIDs
|
||||
eaton: {
|
||||
POWER_STATUS: '1.3.6.1.4.1.534.1.1.2.0', // Power status
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.534.1.2.4.0', // Battery capacity in percentage
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.534.1.2.1.0', // Remaining runtime in minutes
|
||||
POWER_STATUS: '1.3.6.1.4.1.534.1.4.4.0', // xupsOutputSource (3=normal/mains, 5=battery)
|
||||
BATTERY_CAPACITY: '1.3.6.1.4.1.534.1.2.4.0', // xupsBatCapacity (percentage)
|
||||
BATTERY_RUNTIME: '1.3.6.1.4.1.534.1.2.1.0', // xupsBatTimeRemaining (seconds)
|
||||
},
|
||||
|
||||