feat(cli,snmp): fix APC runtime unit defaults and add interactive action editing
This commit is contained in:
@@ -0,0 +1,50 @@
|
||||
import type { ISnmpConfig, TRuntimeUnit, TUpsModel } from './types.ts';
|
||||
|
||||
/**
|
||||
* Return the runtime unit that matches the bundled OID set for a UPS model.
|
||||
*/
|
||||
export function getDefaultRuntimeUnitForUpsModel(
|
||||
upsModel: TUpsModel | undefined,
|
||||
batteryRuntime?: number,
|
||||
): TRuntimeUnit {
|
||||
switch (upsModel) {
|
||||
case 'cyberpower':
|
||||
case 'apc':
|
||||
return 'ticks';
|
||||
case 'eaton':
|
||||
return 'seconds';
|
||||
case 'custom':
|
||||
case 'tripplite':
|
||||
case 'liebert':
|
||||
case undefined:
|
||||
if (batteryRuntime !== undefined && batteryRuntime > 10000) {
|
||||
return 'ticks';
|
||||
}
|
||||
return 'minutes';
|
||||
}
|
||||
}
|
||||
|
||||
/**
|
||||
* Convert an SNMP runtime value to minutes using explicit config first, then model defaults.
|
||||
*/
|
||||
export function convertRuntimeValueToMinutes(
|
||||
config: Pick<ISnmpConfig, 'runtimeUnit' | 'upsModel'>,
|
||||
batteryRuntime: number,
|
||||
): number {
|
||||
if (batteryRuntime <= 0) {
|
||||
return batteryRuntime;
|
||||
}
|
||||
|
||||
const runtimeUnit = config.runtimeUnit ||
|
||||
getDefaultRuntimeUnitForUpsModel(config.upsModel, batteryRuntime);
|
||||
|
||||
if (runtimeUnit === 'seconds') {
|
||||
return Math.floor(batteryRuntime / 60);
|
||||
}
|
||||
|
||||
if (runtimeUnit === 'ticks') {
|
||||
return Math.floor(batteryRuntime / 6000);
|
||||
}
|
||||
|
||||
return batteryRuntime;
|
||||
}
|
||||
Reference in New Issue