fix(snmp): correct power status interpretation using OID set mappings
Move power status value interpretation from hardcoded logic to OID set configuration.
Each UPS model now defines its own value mappings (e.g., CyberPower: 2=online, 3=onBattery).

Fixes incorrect status display where UPS showed "On Battery" when actually online.

Changes:
- Add POWER_STATUS_VALUES to IOidSet interface
- Define value mappings for all UPS models (cyberpower, apc, eaton, tripplite, liebert)
- Refactor determinePowerStatus() to use OID set mappings instead of hardcoded values
- CyberPower now correctly interprets value 2 as online (was incorrectly onBattery)
2025-10-19 23:48:13 +00:00

96 lines
3.4 KiB
TypeScript

import type { IOidSet, TUpsModel } from './types.ts';
/**
* OID sets for different UPS models
* Contains mappings between UPS models and their SNMP OIDs
*/
export class UpsOidSets {
/**
* OID sets for different UPS models
*/
private static readonly UPS_OID_SETS: Record<TUpsModel, IOidSet> = {
// Cyberpower OIDs for RMCARD205 (based on CyberPower_MIB_v2.11)
cyberpower: {
POWER_STATUS: '1.3.6.1.4.1.3808.1.1.1.4.1.1.0', // upsBaseOutputStatus
BATTERY_CAPACITY: '1.3.6.1.4.1.3808.1.1.1.2.2.1.0', // upsAdvanceBatteryCapacity (percentage)
BATTERY_RUNTIME: '1.3.6.1.4.1.3808.1.1.1.2.2.4.0', // upsAdvanceBatteryRunTimeRemaining (TimeTicks)
POWER_STATUS_VALUES: {
online: 2, // upsBaseOutputStatus: 2=onLine
onBattery: 3, // upsBaseOutputStatus: 3=onBattery
},
},
// APC OIDs
apc: {
POWER_STATUS: '1.3.6.1.4.1.318.1.1.1.4.1.1.0', // upsBasicOutputStatus
BATTERY_CAPACITY: '1.3.6.1.4.1.318.1.1.1.2.2.1.0', // Battery capacity in percentage
BATTERY_RUNTIME: '1.3.6.1.4.1.318.1.1.1.2.2.3.0', // Remaining runtime in minutes
POWER_STATUS_VALUES: {
online: 2, // upsBasicOutputStatus: 2=onLine
onBattery: 3, // upsBasicOutputStatus: 3=onBattery
},
},
// Eaton OIDs
eaton: {
POWER_STATUS: '1.3.6.1.4.1.534.1.4.4.0', // xupsOutputSource
BATTERY_CAPACITY: '1.3.6.1.4.1.534.1.2.4.0', // xupsBatCapacity (percentage)
BATTERY_RUNTIME: '1.3.6.1.4.1.534.1.2.1.0', // xupsBatTimeRemaining (seconds)
POWER_STATUS_VALUES: {
online: 3, // xupsOutputSource: 3=normal (mains power)
onBattery: 5, // xupsOutputSource: 5=battery
},
},
// TrippLite OIDs
tripplite: {
POWER_STATUS: '1.3.6.1.4.1.850.1.1.3.1.1.1.0', // tlUpsOutputSource
BATTERY_CAPACITY: '1.3.6.1.4.1.850.1.1.3.2.4.1.0', // Battery capacity in percentage
BATTERY_RUNTIME: '1.3.6.1.4.1.850.1.1.3.2.2.1.0', // Remaining runtime in minutes
POWER_STATUS_VALUES: {
online: 2, // tlUpsOutputSource: 2=normal (mains power)
onBattery: 3, // tlUpsOutputSource: 3=onBattery
},
},
// Liebert/Vertiv OIDs
liebert: {
POWER_STATUS: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.2.1', // lgpPwrOutputSource
BATTERY_CAPACITY: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.4.1', // Battery capacity in percentage
BATTERY_RUNTIME: '1.3.6.1.4.1.476.1.42.3.9.20.1.20.1.2.1.5.1', // Remaining runtime in minutes
POWER_STATUS_VALUES: {
online: 2, // lgpPwrOutputSource: 2=normal (mains power)
onBattery: 3, // lgpPwrOutputSource: 3=onBattery
},
},
// Custom OIDs (to be provided by the user)
custom: {
POWER_STATUS: '',
BATTERY_CAPACITY: '',
BATTERY_RUNTIME: '',
},
};
/**
* Get OID set for a specific UPS model
* @param model UPS model name
* @returns OID set for the model
*/
public static getOidSet(model: TUpsModel): IOidSet {
return this.UPS_OID_SETS[model];
}
/**
* Get standard RFC 1628 OID set as fallback
* @returns Standard OID set
*/
public static getStandardOids(): Record<string, string> {
return {
'power status': '1.3.6.1.2.1.33.1.4.1.0', // upsOutputSource
'battery capacity': '1.3.6.1.2.1.33.1.2.4.0', // upsEstimatedChargeRemaining
'battery runtime': '1.3.6.1.2.1.33.1.2.3.0', // upsEstimatedMinutesRemaining
};
}
}